MACHINE HOURS actual

2010 VISIT E7 SHIRTS CYLINDER HEADS PISTONS PALLIERS 48000 h

INTERSEASON -2013-2014 66334 h

2014 VISIT E5 CYLINDER HEADS TURBOS EXCHANGERS

2014 COGENERATION MANAGEMENT AUTOMATE REPLACEMENT 66734 h

INTERSEASON -2014-2015 69,559 h

COMPLETE CABINET REPLACEMENT COGENERATION MANAGEMENT

HYDRAULIC REVISION

EXCHANGER PUMPS

ACTUATOR OVERHAUL

GAS MIXER OVERHAUL

INTERSEASON -2015-2016 72,784 h

BASIC REVISION

 

INTERSEASON -2016-2017 73014 h

BASIC REVISION

 

INTERSEASON -2017-2018 76,456 h

basic overhaul with catalysts

 

INTERSEASON -2018-2019 79,898 h

revision E 6

 

POSITIVE END OF CONTRACT 10/2019 83340 h

INTERSEASON -2019-2020 86,782 h

INTERSEASON -2020-2021 90,224 h

INTERSEASON -2021-2022 93 666 h

INTERSEASON -2022-2023

TERMINATION OF CONTRACT WITH ERDF 97108 h

END OF COGE CONTRACT BETWEEN CH GRASSE AND ERDF February 28, 2023

 

 

17/10/2017 1 hour test load in the morning

Valve height reading X on 2/2/05 with no pronounced wear

Endoscopic visit X on 2/2/05 with no pronounced wear

Motor tuning

Electrical inspection of motor connectors, probes

Electric auxiliary cabinet visit

Electrical inspection of the motor control control cabinet

Electrical inspection of alternator diodes, regulator,

connections, power tightening, cleaning, lubrication,

alternator insulation check

Control and testing of auxiliary pumps, variators

Control and test of alarm referrals

DEIE proper functioning check

heating circuit expansion compensators

Resume tightening joint dilato cogé + put

nut missing

Replace cogeneration inlet air filters

Resumption of leaks 16 furnaces

Put the 2000W resistance preheating back into service

3phases bol resistance repaired to reassemble

Local cleaning

Reassembly of the high engine air part, seals delivered

Remove the 2 catalyst exhaust filters and the

send for cleaning and review CDEM x deposited to be cleaned

Reassembly of the exhaust catalyst delivery on 25/09

Fit the DRAIN CARTER collection tray

BUS O 16bars 220v 1 inch solenoid valves APPOINT

OIL REPLACE X

Replacement of the high engine air gaskets supplied 1243 0103 Q = 4

 

Replacement of the 4-level oil make-up sensor Level-low

high default delivered ref 1214 0789

 

Oven sealing paste supplied loctite 572

check New oil for the season Remaining: ,,,,,,,,,,,,,,,, L

check Used oil Remaining: ,,,,,,,,,,,,,,,, L

2 E4 lots for the 2017/2018 season x

 

Book

 

aero control: engine, glycol

 

COGENERATION

 

 

Heating level sensors Replacement of the control sensor

 

and tests

 

SYR sensor

932.1

Engine water level sensor Replacement of the control sensor

 

and tests

 

SYR sensor

931

 

cogeneration valve in the boiler room Replace the valve with

 

PROSERV

 

Motor circuit expansion vessel Checking and resuming pressures P air recharge:

 

0.5b

Aero circuit expansion vessel Pressure control and recovery Air precharge

0.7b

 

Double circuit pumps Motor Inspection and testing

Pamont: 0.8b

Paval: 2.2b

?p:

I1: 9.1A

I2: 8.9A

I3: 9.1A

Heating circuit pump Checks and tests

Pamont: 1b

Paval: 3.8b

?p:

I1: 9.7A

I2: 9.8

I3: 9.8

 

- 2 -

 

Aero circuit pump Checking and testing

Pamont: 0b

Paval: 2b

?p:

I1: 15A

I2: 14.8

I3: 14.5

Oil pre-greasing pump I1: 0.2A

I2: 0.2A

I3: 0.2A

Prelub a 2b

AERO exchanger Inspection and testing

Heating circuit

Pamont: 0.8b

Paval: 1b

 0.2b

Engine exchanger Engine circuit

Pamont: 1,2b

Paval: 1.6b

Heating circuit

Pamont: 1.1b

Paval: 1,2b

ü 0.1B

 

MATERIAL DETAIL OF WORK CARRIED OUT REMARKS

Motor dilato Replacement of input and output dilato

 

motor

dilato Visual inspection

Air inlet filtration Replacement of 40 ml Appro filters

For 3 seasons

 

 

1 HYDRAULIC PART COGENERATION

MATERIAL DETAIL OF WORK CARRIED OUT REMARKS

Motor circulation pump

 

Complete revision in the workshop

Mechanical seals

Body seal

Lantern seal

Screws

Ball bearings

 

See report

ETS repair

Maria

 

Double heating circuit pump

 

Complete overhaul in the workshop

Mechanical seals

Body seal

Lantern seal

Screws

Ball bearings

 

See report

ETS repair

Maria

 

Air heater circuit pump Complete overhaul in the workshop

Mechanical seals

Body seal

Lantern seal

Screws

Ball bearings

 

See report

ETS repair

Maria

 

3 Local cogeneration pumps Supply and installation of upstream ?P reading kit

 

/downstream

Exchanger Motor Descaling

 

Checking the tightening of the flanges

Flue gas exchanger Chemical descaling on the raw water side and

exhaust side linkage

Checking the tightening of the flanges

 

Aero exchanger Descaling

 

Checking the tightening of the flanges

Heating circuit part cogé output Pipe corrosion protection

 

Heat insulating

Recapping the excavation

 

There remains the resumption of

concrete on the

car park

 

3 exchangers Replacement of pressure taps

Supply of a case of

pressure tap with flexible hoses

 

- 2 -

 

MATERIAL DETAIL OF WORK CARRIED OUT REMARKS

Motor expansion vessel Replacement

Energy meter Regulatory visit by ITRON

 

2 ENGINE

LEAK FROM CANDLE WELL

ü Removal and re-sealing of the 16 spark plug wells

Resumption on thread with sealing paste black silicone type

 

TYPE E4 visit

 

ü Engine oil change

ü Rocker arm adjustment

ü Filtration replacement

ü Replacement of the 16 spark plugs

ü Replacing the air filters

Supply: Lot MWM E4

 

HEINZMANN actuator type StG30-01.

ü Removal of the actuator

ü Manufacturer overhaul in a specialized workshop (diesel irm)

-Replacement of all wear parts

Mechanical parts

Electric motor

Platinum and Circuit Feedback

passage to the bench, adjustment, painting.

 

Motor circuit electrical conduits

ü Removal of the 4 ducts

ü Control by manufacturer CNR in Marseille

ü Passage to the test bench

GAS mixer

ü Removal of the gas mixer for repair of guide groove by grinder.

ü Reassembly and testing 

 

Best Regards,

 

Mathieu

 

SNVI ENERGY GRAPHIC SASU

Siège social : 2  Rue de la fraternité - 93230 ROMAINVILLE - France  

SIRET 83067130100018 - R.C.S. Bobigny

N° TVA intracommunautaire : FR10 830671301 Code APE 4690Z - EORI : FR83067130100018

To see the contact details please Login or Register
Contact Name:
Company Name:
Mobile Phone:
Phone:
Fax:
Country:
E-Mail:
Web:

Comments      Add New Message

Leave a reply

Replace the security code

We use cookies to improve your experience. By continuing to use our site, you accept our Cookies, Privacy Policy,Terms and Conditions. Close X